www.milbankpowergen.com
Industrial Generators
GSW Series | 70kW - 200kW Perkins Series
Model Number GSW70P GSW90P GSW120P GSW160P GSW200P
480V (3 Phase)
PRIME POWER PRP 58 (73) kW (kVA) 74 (93) kW (kVA) 91 (114) kW (kVA) 125 (156) kW (kVA) 161 (201) kW (kVA)
EMER POWER LTP 64 (80) kW (kVA) 82 (103) kW (kVA) 100 (125) kW (kVA) 142 (177) kW (kVA) 178 (223) kW (kVA)
Voltage 480/277 Volt 480/277 Volt 480/277 Volt 480/277 Volt 480/277 Volt
Frequency 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz
Power factor 0.8 Cos 0.8 Cos 0.8 Cos 0.8 Cos 0.8 Cos
208V (3 Phase)
PRIME POWER PRP 56 (70) kW (kVA) 74 (92) kW (kVA) 90 (113) kW (kVA) 124 (155) kW (kVA) 160 (200) kW (kVA)
EMER POWER LTP 58 (73) kW (kVA) 82 (102) kW (kVA) 96 (120) kW (kVA) 140 (175) kW (kVA) 175 (219) kW (kVA)
Voltage 208/120 Volt 208/120 Volt 208/120 Volt 208/120 Volt 208/120 Volt
Frequency 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz
Power factor 0.8 Cos 0.8 Cos 0.8 Cos 0.8 Cos 0.8 Cos
240V (1 Phase)
PRIME POWER PRP 45 (45) kW (kVA) 68 (68) kW (kVA) 68 (68) kW (kVA) 96 (96) kW (kVA) 123 (123) kW (kVA)
EMER POWER LTP 50 (50) kW (kVA) 74 (74) kW (kVA) 74 (74) kW (kVA) 106 (106) kW (kVA) 136 (136) kW (kVA)
Voltage 240/120 Volt 240/120 Volt 240/120 Volt 240/120 Volt 240/120 Volt
Frequency 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz
Power factor 1 Cos 1 Cos 1 Cos 1 Cos 1 Cos
Tank capacity 92 US Gallons 92 US Gallons 92 US Gallons 92 US Gallons 92 US Gallons
Autonomy (III) (75% PRP) 25.5 h 21.3 h 18.1 h 12.4 h 9.7 h
Autonomy (III) (100% PRP) 19.1 h 16 h 13.6 h 9.3 h 7.3 h
Dimensions (LxWxH) 106.7" x 46.5" x 60.4" 106.7" x 46.5" x 60.4" 106.7" x 46.5" x 66.3" 133.9" x 49.2" x 66.1" 133.9" x 49.2" x 66.1"
Weight (dry) 3,019 lbs 3,281 lbs 3,285 lbs 4,573 lbs 4,880 lbs
DIESEL ENGINE PERKINS 1104D-E44TG PERKINS 1104D-E44TAG1 PERKINS 1104D-E44TAG2 PERKINS 1106D-E66TAG2 PERKINS 1106D-E66TAG4
Exhaust emissions EPA III EPA III EPA III EPA III EPA III
Cooling system Water Water Water Water Water
Speed 1800 rpm 1800 rpm 1800 rpm 1800 rpm 1800 rpm
Displacement 269.1 cu. in. 269.1 cu. in. 269.1 cu. in. 402.7 cu. in. 402.7 cu. in.
Cylinders and disposition 4 line n° disp. 4 line n° disp. 4 line n° disp. 6 line n° disp. 6 line n° disp.
Aspiration Turbo Turbo-Intercooler Turbo-Intercooler Turbo-Intercooler Turbo-Intercooler
Engine power PRP 87 bhp 110 bhp 134 bhp 182 bhp 233 bhp
Engine power LTP 97 bhp 122 bhp 149 bhp 207 bhp 259 bhp
Fuel cons (III) (75% load PRP) 3.6 gal/h 4.3 gal/h 5.1 gal/h 7.5 gal/h 9.5 gal/h
Fuel cons (III) (100% load PRP) 4.8 gal/h 5.8 gal/h 6.8 gal/h 10 gal/h 12.7 gal/h
Specic consumption PRP 0.383 lb/hph 0.363 lb/hph 0.35 lb/hph 0.377 lb/hph 0.376 lb/hph
Engine governor (standard) Mechanical Electronic Electronic Electronic Electronic
SYNCH. ALTERNATOR STAMFORD UCI 224 E STAMFORD UCI 274 C STAMFORD UCI 274 C STAMFORD UCI 274 E STAMFORD UCI 274 G
Power at 27ºC (480V) 64 (80) Kwe (kVA) 110 (138) Kwe (kVA) 110 (138) Kwe (kVA) 155 (194) Kwe (kVA) 203 (253) Kwe (kVA)
Power at 27ºC (208V) 58 (73) Kwe (kVA) 96 (120) Kwe (kVA) 96 (120) Kwe (kVA) 140 (175) Kwe (kVA) 175 (219) Kwe (kVA)
Power at 27ºC (240V) 36 (45) Kwe (kVA) 54 (68) Kwe (kVA) 54 (68) Kwe (kVA) 77 (96) Kwe (kVA) 99 (123) Kwe (kVA)
Insulation H H H H H
Mechanical protection IP23 IP23 IP23 IP23 IP23
Voltage regulation Electronic / 1.0% Electronic / 1.0% Electronic / 1.0% Electronic / 1.0% Electronic / 1.0%
Note: Technical characteristics listed are not inclusive of any product customizations and the producer reserves the right to modify them for innovations without prior notice.
PRODUCT SPECIFICATIONS
27