www.milbankpowergen.com
Model Number MG07002 - 7kW MG10001 - 10kW MG12001 - 12kW MG15001 - 15kW MG20002 - 20kW MG30001 - 30kW MG45001 - 45kW
Watts LP/NG
7,000W (LP) /
6,000W (NG)
10,000W (LP) /
9,000W (NG)
12,000W (LP) /
11,000W (NG)
15,000W (LP) /
14,000W (NG)
20,000W (LP) /
18,000W (NG)
30,000W (LP) /
27,000W (NG)
45,000W (LP) /
45,000W (NG)
Operation Fully Automatic
Engine
504cc Extended
Life Series™
570cc Vanguard™
V-Twin
627cc Vanguard™
V-Twin
895cc Vanguard™
V-Twin
993cc Vanguard™
V-Twin
GM Vortec 3.0L
Inline 4 Cylinder
GM Vortec 5.0L V8
Operating RPM 3600 1800
Voltage 120/240V AC, Single Phase, 1.0 pf
120/240V AC, Single Phase,
Electronic Regulation
Amps LP/NG 29.1 (LP) / 25 (NG)
41.7 (LP) / 37.5 (NG)
50 (LP) / 45.8 (NG)
62.5 (LP) / 58.3 (NG)
83.3 (LP) / 75 (NG)
125 (LP) / 112.5 (NG)
187.5 (LP) / 187.5
(NG)
Alternator Type Automatic Voltage Regulator 4-Pole, Brushless
Oil Warmer Yes (included) Yes (optional - sold separately)
Battery Warmer Yes (optional - sold separately) No
Full Pressure Lubrication
Yes
Fuel Type
Propane (LP vapor),
Natural Gas
Fuel Consumption (at
1
⁄2 load)
33 FT
3
/HR LP,
80 FT
3
/HR NG
35 FT
3
/HR LP,
84 FT
3
/HR NG
41 FT
3
/HR LP,
102 FT
3
/HR NG
56 FT
3
/HR LP,
126 FT
3
/HR NG
71 FT
3
/HR LP,
160 FT
3
/HR NG
92 FT
3
/HR LP,
259 FT
3
/HR NG
178 FT
3
/HR LP,
483 FT
3
/HR NG
Weekly Exerciser Yes
Sound Attenuation Lo Tone™ Mufer Sound Shield™ Technology
Sound Rating
(normal operation)
74 dB 71 dB 65 dB 65 dB 68 dB 65 dB 66 dB
Battery Charger Yes
Overcrank Protection Yes
Diagnotic Alerts with
Remote System Status
Low Oil Pressure, Fail to Start, Low Frequency, Engine Overspeed, Low Voltage, Low Battery, High Temperature, Transfer Switch
Dimensions (L x W x H) 32" x 32.25" x 38.5" 48.69" x 33.75" x 31.63"
84.5" x 39.5" x
41.5"
98.5" x 39.5" x
44.5"
Weight (generator only) 299 lbs. 335 lbs. 470 lbs. 544 lbs. 572 lbs. 1,800 lbs. 2,100 lbs.
Main Line Circuit Breaker
30 Amp 50 Amp 60 Amp 70 Amp 100 Amp 150 Amp 200 Amp
Battery Requirements** 33 Amp Hour, 12 Volt DC, 350 CCA, AGM 50 Amp Hour, 12 Volt DC, 600 CCA, AGM 55 Amp Hour, 12 Volt DC, 650 CCA, AGM
Total Harmonic Distortion
Less than 5%
Limited Warranty 2 Years 3 Years 4 Years
Model Number MG0503120 MG1003162 MG1003002 MG2003002 MG1003992 MG2003992 MG2003993*
Circuits 12 16 Whole House
Amps 50A 100A 100A 200A 100A 200A 200A
Service Entrance
Disconnect
No No No No Yes Yes Yes
Dimensions (L x W x H) 14.25" x 6" x 21" 14” x 6” x 24” 12” x 6” x 16” 12” x 6” x 22” 16” x 7” x 22” 16” x 7” x 30” 33” x 10.25” x 19”
Weight 29 lbs. 39 lbs. 24 lbs. 37 lbs. 38 lbs. 64 lbs. 64 lbs.
Common Features
120/240 Voltage, 2 Poles, 50/60 Frequency, NEMA 3R Enclosure, UL 1008 Listed
Power Mgmt. Method ACCM-II, Patented A/C Power Control Module™
NOTE: Other manufacturers may not be compatible with Milbank’s generators or automatic transfer switches.
* For liquid-cooled models only. **Battery not included